当前位置:首页 > 品牌中心 > 产品详情

模拟量输入模块FB3202B1

HART Transmitter Power Supply, Input Isolator FB3202B1

FB3202B1
  • 1-channel

  • Input Ex ia

  • Installation in suitable enclosures in Zone 1

  • Module can be exchanged under voltage (hot swap)

  • Power supply for 2-wire transmitters with 4 mA ... 20 mA

  • HART communication via field bus or service bus

  • Simulation mode for service operations (forcing)

  • Line fault detection (LFD) and Live Zero monitoring

  • Permanently self-monitoring

  • Supply circuit 15 V (20 mA)

参数表节选:的技术参数              FB3202B1

Slots
Occupied slots1
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation0.75 W
Power consumption1.1 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Analog input
Number of channels1
Suitable field devices

Field devicepressure converter

Field device [2]flow converter

Field device [3]level converter

Field device [4]Temperature Converter
Field device interface

Connection2-wire transmitter
Connection2-wire transmitter (HART):
supply circuit: 2/3+, 4/5-
Transmitter supply voltagemin. 15 V at 20 mA ;  21.5 V at 4 mA
Input resistance15 Ω (terminals 5, 6)

 

236 Ω (terminals 1, 6) HART
Line fault detectioncan be switched on/off for each channel via configuration tool , configurable via configuration tool

Short-circuitfactory setting: > 22 mA configurable between 0 ... 26 mA

Open-circuitfactory setting: < 1 mA configurable between 0 ... 26 mA
HART communicationyes
HART secondary variableyes
Transfer characteristics
Deviation

After calibration0.1 % of the signal range at 20 °C (68 °F)

Influence of ambient temperature0.1 %/10 K of the signal range
Resolution12 Bit (0 ... 26 mA)
Refresh time100 ms
Indicators/settings
LED indicationPower LED (P) green: supply
Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit
Status LED (1) red: line fault (lead breakage or short circuit)
Status LED (2) yellow: Live Zero monitoring
Codingoptional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2007
Degree of protectionIEC 60529:2000
Environmental testEN 60068-2-14:2009
Shock resistanceEN 60068-2-27:2009
Vibration resistanceEN 60068-2-6:2008
Damaging gasEN 60068-2-42:2003
Relative humidityEN 60068-2-78:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionremovable front connector with screw flange (accessory)
wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2)
Massapprox. 350 g
Dimensions28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificateBVS 12 ATEX E 015 X

MarkingEx-Hexagon II 2(1) G Ex d [ia Ga] IIC T4 Gb
Ex-Hexagon II (1) D [Ex ia Da] IIIC
Supply

Voltage27 V

Current87 mA

Power575 mW (linear characteristic)
Galvanic isolation

Input/power supply, internal bussafe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
International approvals
ATEX approvalBVS 12 ATEX E 015 X
INMETROBrazil: TÜV 14.1595X
Marine approval

Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.


上一篇模拟量输入模块 FB3305B2

下一篇没有了

在线客服
热线电话
021-59580007
17701875118
>
微信账号