Speed monitoring up to 40 kHz
1 pre-select value with relay output and LED indicator
2-, 3-, 4-wire and NAMUR sensors as well as rotary encoder connectable
Start-up delay
Menu driven operation via 4 front keys
Period measurement
Output signal can be inverted
Display devices can be set between
| 产品阐述 | ||
|---|---|---|
| Rotation Speed Monitor | ||
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Functional safety related parameters | ||
| MTTFd | 100 a | |
| Supply | ||
| Rated voltage | 200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz  20 VDC ... 30 VDC  | |
| Fusing | external fusing 4 A | |
| Power consumption | AC: < 5 VA DC: < 5 W  | |
| Input | ||
| Connection side | field side | |
| Input 1 | ||
| Connection | terminals 8-, 9+ | |
| Connectable sensor types | NAMUR sensors according to DIN EN 60947-5-6 | |
| Open loop voltage | 8.2 V DC | |
| Short-circuit current | 6.5 mA | |
| Switching point | 1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA | |
| Input frequency | 0.002 ... 10000 Hz, pulse length/duration: ≥ 20µs | |
| Impedance | 1.2 kΩ | |
| Input 2 | ||
| Switching point | high: 16 ... 30 V DC; max.10 mA due to integrated constant current sink; Ri ≅ 3 kΩ low: 0 ... 6 V DC  | |
| Input frequency | 0.002 ... 40000 Hz, pulse length/duration: ≥ 12µs | |
| Connection | terminals 7+, 13- sensor supply terminals 14, 15 NPN/PNP input (galvanically isolated)  | |
| Connectable sensor types | Two, three, or four-wire proximity switch, incremental rotary encoder, or externally generated pulses 16 ... 30 V | |
| Sensor supply | 19 ... 28 V DC non-stabilised; ≤ 30 mA short-circuit protected | |
| Input 3 | ||
| Start-up override | Triggering by external signal 16 ... 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged) | |
| Jumpering time | 0.1 ... 999.9 s (External trigger signal) | |
| Output | ||
| Connection side | control side | |
| Relay | 1 changeover contact  NO, NC, COM  | |
| Sensor supply | 24 V DC ± 10 %, 30 mA , short-circuit protected | |
| Contact loading | 250 V AC/2 A/ cos φ ≥ 0.7 40 V DC/2 A  | |
| Delay | ≤ 20 ms (incl. calculation time) | |
| Mechanical life | ≥ 30.000.000 switching cycles | |
| Transfer characteristics | ||
| Changing interval | 5 ms (Internal processing time) | |
| Time delay before availability | ≤ 400 ms | |
| Measuring error | 0 ... 40000 Hz: ≤ ±0,10%  Display: ±1 digit  | |
| Timer function | ON-delay, OFF-delay, one shot, pulse extension | |
| Time | 0 ... 999.9 s ; mode of operation reversible | |
| Indicators/settings | ||
| Display elements | display , 4-digit, 7-segment red display, 7 mm digit height and LED | |
| LED indication | yellow LED : switching state | |
| Display indication | 0.002 ... 9999 Hz or  0,01 ... 9999 min-1  | |
| Control elements | Control panel | |
| Configuration | via operating buttons | |
| Labeling | space for labeling at the front | |
| Standard conformity | ||
| Electromagnetic compatibility | acc. to EN 50081-2 / EN 50082-2 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 40 °C (-13 ... 104 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | max. 80 %, not condensing | |
| Altitude | 0 ... 2000 m | |
| Operating conditions | The device has only to be used in an indoor area. | |
| Mechanical specifications | ||
| Connection assembly | Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device. | |
| Degree of protection | IP20 | |
| Connection | coded, removable terminals , max. core cross section 0.34 ... 2.5 mm2 | |
| Construction type | modular terminal housing in Makrolon, System KF  For use in the switch cabinet/switch cabinet module  | |
| Mounting | snap-on to 35 mm standard rail or screw fixing | |
| General information | ||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
上一篇没有了