当前位置:首页 > 品牌中心 > 产品详情

KFD2-UFC-Ex1.D

Frequency Converter with Trip Values KFD2-UFC-Ex1.D

KFD2-UFC-Ex1.D
  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Input for NAMUR sensors or dry contacts

  • Input frequency 1 mHz ... 5 kHz

  • Current output 0/4 mA ... 20 mA

  • Relay contact and transistor output

  • Start-up override

  • Line fault detection (LFD)

  • Up to SIL 2 acc. to IEC 61508/IEC 61511

  • 参数表节选:的技术参数              KFD2-UFC-Ex1.D

  • 产品阐述
    24 V DC
  • General specifications
    Signal typeDigital Input
    Functional safety related parameters
    Safety Integrity Level (SIL)SIL 2
    Supply
    Connectionterminals 23+, 24- or power feed module/Power Rail
    Rated voltage20 ... 30 V DC
    Rated currentapprox. 100 mA
    Power dissipation/power consumption≤ 2 W / 2.2 W
    Interface
    Programming interfaceprogramming socket
    Input
    Connection sidefield side
    ConnectionInput I:  intrinsically safe: terminals 1+, 3-
    Input II:  non-intrinsically safe: terminals 13+, 14-
    Input Isensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
    Pulse duration> 50 µs
    Input frequency0.001 ... 5000 Hz
    Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
    Input IIstartup override: 1 ... 1000 s, adjustable in steps of 1 s
    Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
    Open circuit voltage/short-circuit current18 V / 5 mA
    Output
    Connection sidecontrol side
    Connectionoutput I: terminals 10, 11, 12
    output II: terminals 16, 17, 18
    outout III: terminasl 19+, 20-
    output IV: terminals 8+, 7-
    Output I, IIsignal, relay
    Contact loading250 V AC / 2 A / cos φ ≥ 0.7  ; 40 V DC / 2 A
    Mechanical life5 x 107 switching cycles
    Energized/De-energized delayapprox. 20 ms / approx. 20 ms
    Output IIIelectronic output, passive
    Contact loading40 V DC
    Signal level1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
    0-signal: switched off (off-state current ≤ 10 µA)
    Output IVanalog
    Current range0 ... 20 mA or 4 ... 20 mA
    Open loop voltagemax. 24 V DC
    Loadmax. 650 Ω
    Fault signaldownscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
    Collective error messagePower Rail
    Transfer characteristics
    Input I
    Measurement range0.001 ... 5000 Hz
    Resolution0.1 % of the measurement value , ≥ 0.001 Hz
    Accuracy0.1 % of the measurement value , > 0.001 Hz
    Measuring time< 100 ms
    Influence of ambient temperature0.003 %/K (30 ppm)
    Output I, II
    Response delay≤ 200 ms
    Output IV
    Resolution< 10 µA
    Accuracy< 20 µA
    Influence of ambient temperature0.005 %/K (50 ppm)
    Galvanic isolation
    Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
    Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
    Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
    Output III/power supply and collective errorbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
    Output III/start-up overridebasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
    Output III/IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
    Output IV/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
    Start-up override/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
    Interface/power supply and collective errorfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
    Interface/output IIIbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
    Indicators/settings
    Display elementsLEDs , display
    Control elementsControl panel
    Configurationvia operating buttons
    via PACTware
    Labelingspace for labeling at the front
    Directive conformity
    Electromagnetic compatibility
    Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
    Low voltage
    Directive 2014/35/EUEN 61010-1:2010
    Conformity
    Electromagnetic compatibilityNE 21:2006
    Degree of protectionIEC 60529:2001
    InputEN 60947-5-6:2000
    Ambient conditions
    Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
    Mechanical specifications
    Degree of protectionIP20
    Connectionscrew terminals
    Mass300 g
    Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
    Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
    Data for application in connection with hazardous areas
    EU-type examination certificateTÜV 99 ATEX 1471
    MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
    Ex-Hexagon II (1)D [Ex ia Da] IIIC
    Ex-Hexagon I (M1) [Ex ia Ma] I
    Supply
    Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
    Input Iterminals 1+, 3-: Ex ia
    VoltageUo10.1 V
    CurrentIo13.5 mA
    PowerPo34 mW (linear characteristic)
    Input IIterminals 13+, 14- non-intrinsically safe
    Maximum safe voltageUm40 V (Attention! The rated voltage can be lower.)
    Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
    Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
    Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
    Output IIIterminals 19+, 20- non-intrinsically safe
    Maximum safe voltageUm40 V (Attention! Um is no rated voltage.)
    Output IVterminals 8+, 7- non-intrinsically safe
    Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
    InterfaceRS 232
    Maximum safe voltage40 V (Attention! Um is no rated voltage.)
    CertificateTÜV 02 ATEX 1885 X
    MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
    Output I, II
    Contact loading50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
    Galvanic isolation
    Input I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
    Directive conformity
    Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
    International approvals
    FM  approval
    Control drawing16-538FM-12
    UL approvalE223772
    IECEx approvalIECEx TUN 04.0007
    Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
    General information
    Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.