当前位置:首页 > 品牌中心 > 产品详情

KFA6-DWB-Ex1.D

Rotation Speed Monitor KFA6-DWB-Ex1.D

KFA6-DWB-Ex1.D
  • 1-channel isolated barrier

  • 230 V AC supply

  • Dry contact or NAMUR inputs

  • Input frequency 1 mHz ... 5 kHz

  • 2 relay contact outputs

  • Start-up override

  • Configurable by keypad

  • Line fault detection (LFD)

  • Up to SIL 2 acc. to IEC 61508/IEC 61511

参数表节选:的技术参数              KFA6-DWB-Ex1.D

产品阐述
230 V AC
General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 23, 24
Rated voltage230 V AC ± 10 %
Rated current18 mA
Power dissipation/power consumption≤ 2 VA / 2 VA
Input
Connection sidefield side
ConnectionInput I:  intrinsically safe: terminals 1+, 3-
Input II:  non-intrinsically safe: terminals 13+, 14-
Input Iacc. to EN 60947-5-6 (NAMUR)
Pulse duration> 50 µs
Input frequency0.001 ... 5000 Hz
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input IIstartup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/PassiveI > 4 mA (for min. 100 ms)/ I < 1 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7  ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateTÜV 99 ATEX 1408
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
CertificateTÜV 02 ATEX 1885 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
Output I, II
Contact loading50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM  approval
Control drawing16-538FM-12
UL approvalE223772
IECEx approvalIECEx TUN 03.0000
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

上一篇KFD2-UFC-Ex1.D

下一篇KFD2-SR2-Ex2.W.SM

在线客服
热线电话
021-59580007
17701875118
>
微信账号